Other Settings
37
Changing the Heating Pattern of the Boiler (continued)
“Remote control” is displayed
Cause
Remedy
A remote control is connected to the heating
circuit.
Make adjustments or carry out s cans at the remote control (see
separate operating instructions).
”Ext. control” is displayed
Cause
Remedy
The heating program se t at the control unit was
changed over by an external device
(e.g. connection extension).
No action required. The heating program changeover was manually
selected.
”Ext. program” is displayed
Cause
Remedy
The heating program se t at the control unit was
changed over by the Vitocom 100 communicating
interface (not used).
No action required. The heating program changeover was manually
selected.
Ext.roomt.setpt.isdisplayed
Cause
Remedy
A room set point temperature has been connected
via the communication interface.
No action required. The connection was manually s elected.
”Without function” is displayed
Cause
Remedy
No function is allocated to the key you have
pressed.
No action required. Select appropriate key.